Rated voltage: 40.5 kV
Rated frequency: 50 Hz
Rated current:
Main bus: Usually 1250A, 1600A, 2000A, 2500A, 3150A, etc.
Feeder/incoming line/bus tie circuit: Select according to demand, commonly used 630A, 800A, 1250A, 1600A, 2000A, 2500A, 3150A, etc.
Rated short-time withstand current (thermal stability current - Icw): Usually 25kA, 31.5kA, 40kA (4s), etc.
Rated peak withstand current (dynamic stability current - Ipk): usually 63kA, 80kA, 100kA, etc. (generally 2.5 times of Icw).
Rated short-circuit breaking current (Isc): usually 25kA, 31.5kA, 40kA, etc. (consistent with the equipped circuit breaker).
Rated short-circuit closing current: usually equal to the rated peak withstand current (Ipk).
Rated insulation level:
1min power frequency withstand voltage (phase-to-phase, phase-to-ground): 95 kV
Lightning impulse withstand voltage (peak, phase-to-phase, phase-to-ground): 185 kV
Isolation break withstand voltage: usually higher than the relative ground level (such as power frequency 110kV, impulse 215kV).
Protection level:
Casing: IP4X (prevents solid foreign objects with a diameter greater than 1mm from entering).
When the circuit breaker room door is open: IP2X.
Between internal compartments: usually with metal partitions to ensure a certain degree of isolation.
Main circuit resistance: ≤ specified value (μΩ), the specific value depends on the circuit configuration and current level.
Mechanical life: Circuit breaker trolley: usually 10,000 times; grounding switch: usually 2,000 times; isolating switch (if any): usually 2,000 times.
Dimensions (width x depth x height): Typical dimensions are about 1200mm x 1800mm x 2600mm (single cabinet), but there are large differences between different manufacturers and configurations.