Rated voltage: 12kV / 24kV (main circuit).
Rated current:
Main busbar/load switch: 630A, 1250A (common); up to 1600A or 2000A (specific manufacturer/design).
Fuse circuit (-F combination): usually ≤125A or 200A (with fuse protection transformer).
Rated frequency: 50Hz.
Rated short-circuit breaking current:
Load switch: 20kA, 25kA (effective value).
Fuse: Provides short-circuit breaking capacity (determined by fuse parameters, much higher than load switch).
Rated short-circuit closing current: 50kA, 63kA (peak value).
Rated short-time withstand current (Icw): 20kA / 4s, 25kA / 3s (effective value).
Rated peak withstand current (Ipk): 50kA, 63kA (peak value).
Rated insulation level (typical value of 12kV cabinet):
Power frequency withstand voltage (1min): 42kV to ground/phase-to-phase; 48kV at isolation break.
Lightning impulse withstand voltage: 75kV to ground/phase-to-phase; 85kV at isolation break.
(The value of 24kV cabinet is higher, refer to GB standard)
Main circuit resistance: ≤ design value (such as ≤150μΩ @ 630A, depending on the manufacturer).
Protection level:
Casing: IP4X (anti-≥1mm solid).
Internal compartment: IP2X (proof ≥12.5mm solid).
Fuse cartridge: IP6X (dust-tight).
SF6 gas parameters:
Rated filling pressure: 0.04~0.05 MPa (gauge pressure, at 20℃).
Annual leakage rate: ≤0.5%/year (or ≤1%/year, lower for high-demand designs).
Alarm pressure: usually set at 0.03 MPa.